2006 Alabama Code - Section 25-9-172 — Grounding of frames, casings and other electrical equipment.

Where grounding wires are used to ground metallic sheaths, armors, conduits, frames, casings and other metallic enclosures, such grounding wires must comply with the following conditions:

(1) The cross-sectional area (size) of the grounding wire shall be at least one-half the cross-sectional area (size) of the power conductor where the power conductor used is No. 6 A.W.G. or larger.

(2) Where the power conductor used is less than No. 6 A.W.G., the cross-sectional area (size) of the grounding wire shall be equal to the cross-sectional area (size) of the power conductor.

(Acts 1949, No. 207, p. 242, §41; Acts 1975, 4th Ex. Sess., No. 147, p. 2866, §1.)

Disclaimer: These codes may not be the most recent version. Alabama may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.