§ 23-492.03 Floor, roof and wall openings; guards

AZ Rev Stat § 23-492.03 (2014) What's This?

23-492.03. Floor, roof and wall openings; guards

(Conditionally Rpld.)

A. This section applies to temporary or emergency conditions where there is a danger of employees or materials falling through floor, roof or wall openings or from stairways or runways.

B. Floor, roof and skylight openings shall be guarded by either temporary railings and toeboards or by covers. Temporary railings and toeboards shall meet the requirements of section 23-492.06. The railing shall be provided on all exposed sides, except at entrances to stairways. Covers shall be capable of safely supporting the greater of four hundred pounds or twice the weight of the employees, equipment and materials that may be imposed on any one square foot area of the cover at any time. Covers shall be secured in place to prevent accidental removal or displacement and shall be a pressure sensitized, painted or stenciled sign with legible letters not less than one inch high that states " Opening - Do Not Remove" . Markings of chalk or keel shall not be used.

C. Ladderway floor openings or platforms shall be guarded by standard railings with standard toeboards on all exposed sides, except at the entrance to the opening, with the passage through the railing either provided with a swinging gate or so offset that a person cannot walk directly into the opening.

D. Hatchway and chute floor openings shall be guarded by either:

1. Hinged covers of standard strength and construction and a standard railing with only one exposed side. If the opening is not in use, the cover shall be closed or the exposed side shall be guarded at both top and intermediate positions by removable standard railings.

2. A removable standard railing with toeboard on not more than two sides of the opening and fixed standard railings with toeboards on all other exposed sides. The removable railing shall be kept in place if the opening is not in use and should preferably be hinged or otherwise mounted so as to be conveniently replaceable.

E. Pits and trap door floor openings shall be guarded by floor opening covers of standard strength and construction. If the cover is not in place, the pit or trap openings shall be protected on all exposed sides by movable standard railings.

F. Manhole floor openings shall be guarded by standard covers that need not be hinged in place. If the cover is not in place, the manhole opening shall be protected by standard railings.

G. Temporary floor openings shall have standard railings.

H. Floor holes, into which persons can accidentally walk, shall be guarded by either a standard railing with standard toeboard on all exposed sides, or a floor hole cover of standard strength and construction that is secured against accidental displacement. If the cover is not in place, the floor hole shall be protected by standard railing.

I. Wall openings, from which there is a drop of more than four feet and the bottom of the opening is less than three feet above the working surface, shall be guarded as follows:

1. When the height and placement of the opening in relation to the working surface is such that either a standard rail or intermediate rail will effectively reduce the danger of falling, one or both shall be provided.

2. The bottom of a wall opening, which is less than four inches above the working surface regardless of width, shall be protected by a standard toeboard or an enclosing screen either of solid construction or as otherwise required by this section.

J. An extension platform outside a wall opening onto which materials can be hoisted for handling shall have side rails or equivalent guards of standard specifications. One side of an extension platform may have removable railings in order to facilitate handling materials.

K. This section applies if a chute is attached to an opening, except that a toeboard is not required.

L. Wall opening protection shall meet the following requirements:

1. Barriers shall be of such construction and mounting that, when in place at the opening, the barrier is capable of withstanding a load of at least two hundred pounds applied in any direction except upward.

2. Screens shall be of such construction and mounting that they are capable of withstanding a load of at least two hundred pounds applied horizontally at any point on the near side of the screen. They may be of solid construction, of grill work with openings not more than eight inches long or of slat work with openings not more than four inches wide with length unrestricted.

Disclaimer: These codes may not be the most recent version. Arizona may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.