37-3-303. Activity near overhead line; safety restrictions.


WY Stat § 37-3-303 (through 2012) What's This?

(a) Unless danger against contact with high voltage overhead lines has been effectively guarded against as provided by W.S. 37-3-304 a person or business entity, individually or through an agent or employee or as an agent or employee, shall not:

(i) Require any other person to perform any act if at any time during the performance of the act it is possible that the actor could move or be moved closer to any high voltage overhead line or if it is possible that any part of any tool or material used by the actor could be moved closer to any high voltage overhead line during the performance of the act than the following clearances:

(A) For lines rated fifty (50) kilovolts or less, six (6) feet of clearance;

(B) For lines rated over fifty (50) kilovolts, six (6) feet plus four-tenths (.4) of an inch for each kilovolt over fifty (50) kilovolts.

(ii) Operate any mechanical equipment or hoisting equipment or any load of equipment, any part of which is capable of vertical, lateral or swinging motion closer to any high voltage overhead line than the following clearances:

(A) For lines rated fifty (50) kilovolts or less, ten (10) feet of clearance;

(B) For lines rated over fifty (50) kilovolts, ten (10) feet plus four-tenths (.4) of an inch for each kilovolt over fifty (50) kilovolts.

Disclaimer: These codes may not be the most recent version. Wyoming may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.