35-11-1429. Tank requirements; rulemaking authority.


WY Stat § 35-11-1429 (through 2012) What's This?

(a) Cathodic protection shall be installed and operated on all internally lined underground storage tanks no later than June 30, 2008.

(b) All underground storage tank systems that dispense more than five hundred thousand (500,000) gallons per month of a regulated substance shall be replaced with double wall tanks and lines with interstitial leak monitoring no later than June 30, 2012, or thirty (30) years from the date of installation of the underground storage tank, whichever is later.

(c) Double wall underground storage tanks and lines with interstitial leak monitoring shall be installed whenever any underground storage tank is installed.

(d) Double wall underground storage tank system lines with interstitial leak monitoring shall be installed whenever any line is installed on any underground storage tank system.

(e) The council may promulgate rules and regulations to administer this section after recommendation from the director.

Disclaimer: These codes may not be the most recent version. Wyoming may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.