2012 Utah Code
Title 15A - State Construction and Fire Codes Act
Article 3 - Statewide Amendments Incorporated as Part of State Construction Code
Section 113 - Amendments to Chapters 32 through 35 of IBC.


UT Code § 15A-3-113 (2012) What's This?

15A-3-113. Amendments to Chapters 32 through 35 of IBC.

(1) A new section IBC, Section 3401.7, is added as follows: " 3401.7 Parapet bracing, wall anchors, and other appendages. Until June 30, 2014, a building constructed before 1975 shall have parapet bracing, wall anchors, and appendages such as cornices, spires, towers, tanks, signs, statuary, etc. evaluated by a licensed engineer when the building is undergoing structural alterations, which may include structural sheathing replacement of 10% or greater, or other structural repairs. Reroofing or water membrane replacement may not be considered a structural alteration or repair for purposes of this section. Beginning July 1, 2014, a building constructed before 1975 shall have parapet bracing, wall anchors, and appendages such as cornices, spires, towers, tanks, signs, statuary, etc. evaluated by a licensed engineer when the building is undergoing a total reroofing. Parapet bracing, wall anchors, and appendages required by this section shall be evaluated in accordance with 75% of the seismic forces as specified in Section 1613. When allowed by the local building official, alternate methods of equivalent strength as referenced in an approved code under Utah Code, Subsection 15A-1-204(6)(a), will be considered when accompanied by engineer-sealed drawings, details, and calculations. When found to be deficient because of design or deteriorated condition, the engineer's recommendations to anchor, brace, reinforce, or remove the deficient feature shall be implemented.

Exceptions:

1. Group R-3 and U occupancies.

2. Unreinforced masonry parapets need not be braced according to the above stated provisions provided that the maximum height of an unreinforced masonry parapet above the level of the diaphragm tension anchors or above the parapet braces shall not exceed one and one-half times the thickness of the parapet wall. The parapet height may be a maximum of two and one-half times its thickness in other than Seismic Design Categories D, E, or F."

(2) IBC, Section 3408.4, is deleted and replaced with the following: "3408.4 Seismic. When a change in occupancy results in a structure being reclassified to a higher Risk Category (as defined in Table 1604.5), or when such change of occupancy results in a design occupant load increase of 100% or more, the structure shall conform to the seismic requirements for a new structure.

Exceptions:

1. Specific seismic detailing requirements of this code or ASCE 7 for a new structure shall not be required to be met where it can be shown that the level of performance and seismic safety is equivalent to that of a new structure. A demonstration of equivalence analysis shall consider the regularity, overstrength, redundancy, and ductility of the structure. Alternatively, the building official may allow the structure to be upgraded in accordance with referenced sections as found in an approved code under Utah Code, Subsection 15A-1-204(6)(a).

2. When a change of use results in a structure being reclassified from Risk Category I or II to Risk Category III and the structure is located in a seismic map area where SDS is less than 0.33, compliance with the seismic requirements of this code and ASCE 7 are not required.

3. Where design occupant load increase is less than 25 occupants and the Risk Category does not change."

(3) In IBC, Chapter 35, the referenced standard ICCA117.1-09, Section 606.2, Exception 1 is modified to include the following sentence at the end of the exception:

"The minimum clear floor space shall be centered on the sink assembly."

(4) The following referenced standard is added under UL in IBC, Chapter 35:

"Number

Title

Referenced in code section number

2034-2008

Standard of Single- and Multiple-station Carbon Monoxide Alarms

907.9"


Amended by Chapter 297, 2013 General Session

Disclaimer: These codes may not be the most recent version. Utah may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.