View Our Newest Version Here

2011 Utah Code
Title 15A State Construction and Fire Codes Act
Chapter 3 Statewide Amendments Incorporated as Part of State Construction Code
Section 306 Amendments to Chapter 6 of IPC.

15A-3-306. Amendments to Chapter 6 of IPC.
(1) IPC, Section 602.3, is deleted and replaced with the following: "602.3 Individual water supply. Where a potable public water supply is not available, individual sources of potable water supply shall be utilized provided that the source has been developed in accordance with Utah Code, Sections 73-3-1, 73-3-3, and 73-3-25, as administered by the Department of Natural Resources, Division of Water Rights. In addition, the quality of the water shall be approved by the local health department having jurisdiction. The source shall supply sufficient quantity of water to comply with the requirements of this chapter."
(2) IPC, Sections 602.3.1, 602.3.2, 602.3.3, 602.3.4, 602.3.5, and 602.3.5.1, are deleted.
(3) A new IPC, Section 604.4.1, is added as follows: "604.4.1 Manually operated metering faucets. Self closing or manually operated metering faucets shall provide a flow of water for at least 15 seconds without the need to reactivate the faucet."
(4) IPC, Section 606.5, is deleted and replaced with the following: "606.5 Water pressure booster systems. Water pressure booster systems shall be provided as required by Section 606.5.1 through 606.5.11."
(5) A new IPC, Section 606.5.11, is added as follows: "606.5.11 Prohibited installation. In no case shall a booster pump be allowed that will lower the pressure in the public main to less than 20 psi."
(6) IPC, Table 608.1, is deleted and replaced with the following:
"TABLE 608.1
General Methods of Protection
Assembly (applicable standard) Degree of Hazard Application Installation Criteria
Reduced Pressure Principle Backflow Preventer
(AWWA C511, USC-FCCCHR, ASSE 1013 CSA CNA/CSA-B64.4) and Reduced Pressure Detector Assembly
(ASSE 1047, USC-FCCCHR)
High or Low Backpressure or Backsiphonage
1/2" - 16"
a. The bottom of each RP assembly shall be a minimum of 12 inches above the ground or floor.
b. RP assemblies shall NOT be installed in a pit.
c. The relief valve on each RP assembly shall not be directly connected to any waste disposal line, including sanitary sewer, storm drains, or vents.
d. The assembly shall be installed in a horizontal position only unless listed or approved for vertical installation.
Double Check Backflow Prevention Assembly
(AWWA C510, USC-FCCCHR, ASSE 1015) Double Check Detector Assembly Backflow Preventer (ASSE 1048, USC-FCCCHR)
Low Backpressure or Backsiphonage
1/2" - 16"
a. If installed in a pit, the DC assembly shall be installed with a minimum of 12 inches of clearance between all sides of the vault including the floor and roof or ceiling with adequate room for testing and maintenance.
b. Shall be installed in a horizontal position unless listed or approved for vertical installation.
Pressure Vacuum Breaker Assembly (ASSE 1020, USC-FCCCHR) High or Low Backsiphonage
1/2" - 2"
a. Shall not be installed in an area that could be subjected to backpressure or back drainage conditions.
b. Shall be installed a minimum of 12 inches above all downstream piping and the highest point of use.
c. Shall not be installed below ground or in a vault or pit.
d. Shall be installed in a vertical position only.
Spill Resistant Vacuum Breaker (ASSE 1056, USC-FCCCHR) High or Low Backsiphonage
1/4" - 2"
a. Shall not be installed in an area that could be subjected to backpressure or back drainage conditions.
b. Shall be installed a minimum of 12 inches above all downstream piping and the highest point of use.
c. Shall not be installed below ground or in a vault or pit.
d. Shall be installed in a vertical position only.
General Installation Criteria The assembly owner, when necessary, shall provide devices or structures to facilitate testing, repair, and/or maintenance and to ensure the safety of the backflow technician.
Assemblies shall not be installed more than five feet off the floor unless a permanent platform is installed.
The body of the assembly shall not be closer than 12 inches, to any wall, ceiling or encumbrance, and shall be accessible for testing, repair and/or maintenance.
In cold climates, assemblies shall be protected from freezing by a means acceptable to the code official.
Assemblies shall be maintained as an intact assembly."
(7) IPC, Table 608.1.1, is added as follows:
"TABLE 608.1.1
Specialty Backflow Devices for low hazard use only
Device Degree of Hazard Application Applicable Standard
Air Gap High or Low Backsiphonage See Table 608.15.1
ASME A112.1.2
Antisiphon-type Water Closet Flush Tank Ball Cock Low Backsiphonage ASSE 1002
CSA CAN/
CSA-B125
Atmospheric Vacuum Breaker High or Low Backsiphonage
a. Shall not be installed in an area that could be subjected to backpressure or back drainage conditions.
b. Shall not be installed where it may be subjected to continuous pressure for more than 12 consecutive hours at any time.
c. Shall be installed a minimum of six inches above all downstream piping and the highest point of use.
d. Shall be installed on the discharge (downstream) side of any valves.
e. The AVB shall be installed in a vertical position only.
ASSE 1001
USC-FCCCHR,
CSA CAN/
CSA-B64.1.1
Dual check valve Backflow Preventer Low Backsiphonage or Backpressure
1/4" - 1"
ASSE 1024
Backflow Preventer with Intermediate Atmospheric Vent Low Residential Boiler Backsiphonage or Backpressure
1/4" - 3/4"
ASSE 1012
CSA CAN/
CSA-B64.3
Dual check valve type Backflow Preventer for Carbonated Beverage Dispensers/Post Mix Type Low Backsiphonage or Backpressure
1/4" - 3/8"
ASSE 1022
Hose-connection Vacuum Breaker Low Backsiphonage
1/2", 3/4", 1"
ASSE 1011
CSA CAN/
CSA-B64.2
Vacuum Breaker Wall Hydrants, Frost-resistant, Automatic Draining Type Low Backsiphonage
3/4", 1"
ASSE 1019
CSA CAN/
CSA-B64.2.2
Laboratory Faucet Backflow Preventer Low Backsiphonage ASSE 1035
CSA CAN/
CSA-B64.7
Hose Connection Backflow Preventer Low Backsiphonage
1/2" - 1"
ASSE 1052
Installation Guidelines: The above specialty devices shall be installed in accordance with their listing and the manufacturer's instructions and the specific provisions of this chapter."
(8) In IPC, Section 608.6, the following sentence is added at the end of the paragraph: "Any connection between potable water piping and sewer-connected waste shall be protected by an air gap."
(9) IPC, Section 608.7, is deleted.
(10) In IPC, Section 608.11, the following sentence is added at the end of the paragraph: "The coating and installation shall conform to NSF Standard 61 and application of the coating shall comply with the manufacturer's instructions."
(11) IPC, Section 608.13.3, is deleted and replaced with the following: "608.13.3 Backflow preventer with intermediate atmospheric vent. Backflow preventers with intermediate atmospheric vents shall conform to ASSE 1012 or CSA CAN/CSA-B64.3. These devices shall be permitted to be installed on residential boilers only, without chemical treatment, where subject to continuous pressure conditions. The relief opening shall discharge by air gap and shall be prevented from being submerged."
(12) IPC, Section 608.13.4, is deleted.
(13) IPC, Section 608.13.9, is deleted.
(14) IPC, Section 608.15.3, is deleted and replaced with the following: "608.15.3 Protection by a backflow preventer with intermediate atmospheric vent. Connections to residential boilers only, without chemical treatment, shall be protected by a backflow preventer with an intermediate atmospheric vent."
(15) IPC, Section 608.15.4, is deleted and replaced with the following: "608.15.4 Protection by a vacuum breaker. Openings and outlets shall be protected by atmospheric-type or pressure-type vacuum breakers. The critical level of the atmospheric vacuum breaker shall be set a minimum of 6 inches (152 mm) above the flood level rim of the fixture or device. The critical level of the pressure vacuum breaker shall be set a minimum of 12 inches (304 mm) above the flood level rim of the fixture or device. Fill valves shall be set in accordance with Section 425.3.1. Vacuum breakers shall not be installed under exhaust hoods or similar locations that will contain toxic fumes or vapors. Pipe-applied vacuum breakers shall be installed not less than 6 inches (152 mm) above the flood level rim of the fixture, receptor, or device served. No valves shall be installed downstream of the atmospheric vacuum breaker."
(16) In IPC, Section 608.15.4.2, the following is added after the first sentence: "Add-on-backflow prevention devices shall be non-removable. In climates where freezing temperatures occur, a listed self-draining frost proof hose bibb with an integral backflow preventer shall be used."
(17) In IPC, Section 608.16.2, the first sentence of the paragraph is deleted and replaced as follows: "608.16.2 Connections to boilers. The potable water supply to the residential boiler

only, without chemical treatment, shall be equipped with a backflow preventer with an intermediate atmospheric vent complying with ASSE 1012 or CSA CAN/CSA-B64.3."
(18) IPC, Section 608.16.3, is deleted and replaced with the following: "608.16.3 Heat exchangers. Heat exchangers shall be separated from potable water by double-wall construction. An air gap open to the atmosphere shall be provided between the two walls.
Exceptions:
1. Single wall heat exchangers shall be permitted when all of the following conditions are met:
a. It utilizes a heat transfer medium of potable water or contains only substances which are recognized as safe by the United States Food and Drug Administration (FDA);
b. The pressure of the heat transfer medium is maintained less than the normal minimum operating pressure of the potable water system; and
c. The equipment is permanently labeled to indicate only additives recognized as safe by the FDA shall be used.
2. Steam systems that comply with paragraph 1 above.
3. Approved listed electrical drinking water coolers."
(19) In IPC, Section 608.16.4.1, a new exception is added as follows: "Exception: All class 1 and 2 systems containing chemical additives consisting of strictly glycerine (C.P. or U.S.P. 96.5 percent grade) or propylene glycol shall be protected against backflow with a double check valve assembly. Such systems shall include written certification of the chemical additives at the time of original installation and service or maintenance."
(20) IPC, Section 608.16.7, is deleted and replaced with the following: "608.16.7 Chemical dispensers. Where chemical dispensers connect to the water distribution system, the water supply system shall be protected against backflow in accordance with Section 608.13.1, Section 608.13.2, Section 608.13.5, Section 608.13.6 or Section 608.13.8."
(21) IPC, Section 608.16.8, is deleted and replaced with the following: "608.16.8 Portable cleaning equipment. Where the portable cleaning equipment connects to the water distribution system, the water supply system shall be protected against backflow in accordance with Section 608.13.1, Section 608.13.2 or Section 608.13.8."
(22) A new IPC, Section 608.16.11, is added as follows: "608.16.11 Automatic and coin operated car washes. The water supply to an automatic or coin operated car wash shall be protected in accordance with Section 608.13.1 or Section 608.13.2."
(23) IPC, Section 608.17, is deleted.

Disclaimer: These codes may not be the most recent version. Utah may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.