2011 Utah Code
Title 15A State Construction and Fire Codes Act
Chapter 3 Statewide Amendments Incorporated as Part of State Construction Code
Section 113 Amendments to Chapters 32 through 35 of IBC.

15A-3-113. Amendments to Chapters 32 through 35 of IBC.
(1) A new section IBC, Section 3401.6, is added as follows: "3401.6 Parapet bracing, wall anchors, and other appendages. Buildings constructed before 1975 shall have parapet bracing, wall anchors, and appendages such as cornices, spires, towers, tanks, signs, statuary, etc. evaluated by a licensed engineer when said building is undergoing reroofing, or alteration of or repair to said feature. Such parapet bracing, wall anchors, and appendages shall be evaluated in accordance with 75% of the seismic forces as specified in Section 1613. When allowed by the local building official, alternate methods of equivalent strength as referenced in an approved code under Utah Code, Subsection 15A-1-204(6)(a), will be considered when accompanied by engineer-sealed drawings, details, and calculations. When found to be deficient because of design or deteriorated condition, the engineer's recommendations to anchor, brace, reinforce, or remove the deficient feature shall be implemented.
EXCEPTIONS:
1. Group R-3 and U occupancies.
2. Unreinforced masonry parapets need not be braced according to the above stated provisions provided that the maximum height of an unreinforced masonry parapet above the level of the diaphragm tension anchors or above the parapet braces shall not exceed one and one-half times the thickness of the parapet wall. The parapet height may be a maximum of two and one-half times its thickness in other than Seismic Design Categories D, E, or F."
(2) IBC, Section 3408.4, is deleted and replaced with the following: "3408.4 Change in Occupancy. When a change in occupancy results in a structure being reclassified to a higher Occupancy Category (as defined in Table 1604.5), or when such change of occupancy results in a design occupant load increase of 100% or more, the structure shall conform to the seismic requirements for a new structure.
Exceptions:
1. Specific seismic detailing requirements of this code or ASCE 7 for a new structure shall not be required to be met where it can be shown that the level of performance and seismic safety is equivalent to that of a new structure. Such analysis shall consider the regularity, overstrength, redundancy, and ductility of the structure within the context of the existing and retrofit (if any) detailing providing. Alternatively, the building official may allow the structure to be upgraded in accordance with referenced sections as found in an approved code under Utah Code, Subsection 15A-1-204(6)(a).
2. When a change of use results in a structure being reclassified from Occupancy Category I or II to Occupancy Category III and the structure is located in a seismic map area where SDS is less than 0.33, compliance with the seismic requirements of this code and ASCE 7 are not required.
3. Where design occupant load increase is less than 25 occupants and the Occupancy Category does not change."
(3) In IBC, Section 3411.1, the exception is deleted and replaced with the following: "Exception: Type B dwelling or sleeping units required by Section 1107 of this code are not required to be provided in existing buildings and facilities unless being altered or undergoing a change of occupancy classification."
(4) The following referenced standard is added under NFPA in IBC, Chapter 35:
"Number Title Referenced in code section number
720-09 Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment 907.9"
(5) The following referenced standard is added under UL in IBC, Chapter 35:
"Number Title Referenced in code section number
2034-2008 Standard of Single- and Multiple-station Carbon Monoxide Alarms 907.9"
(6) In IBC, Chapter 35, NFPA referenced standard 10-07 is deleted and replaced with the following:
"Number Title Referenced in code section number
10-10 Portable Fire Extinguishers 906.2, 906.3.2, 906.3.4, Table 906.3(1), Table 906.3(2)"
(7) In IBC, Chapter 35, NFPA referenced standard 11-05 is deleted and replaced with the following:
"Number Title Referenced in code section number
11-10 Low Expansion Foam 904.7"
(8) In IBC, Chapter 35, NFPA referenced standard 12-05 is deleted and replaced with the following:
"Number Title Referenced in code section number
12-08 Carbon Dioxide Extinguishing Systems 904.8, 904.11"
(9) In IBC, Chapter 35, NFPA referenced standard 12A-04 is deleted and replaced with the following:
"Number Title Referenced in code section number
12A-09 Halon 1301 Fire Extinguishing Systems 904.9"
(10) In IBC, Chapter 35, NFPA referenced standard 13-07 is deleted and replaced with the following:
"Number Title Referenced in code section number
13-10 Installation of Sprinkler Systems 708.2, 903.3.1.1, 903.3.2, 903.3.5.1.1, 903.3.5.3, 904.11, 905.3.4, 907.6.3, 1613.3"
(11) In IBC, Chapter 35, NFPA referenced standard 13D-07 is deleted and replaced with the following:
"Number Title Referenced in code section number
13D-10 Installation of Sprinkler Systems in One- and Two-family Dwellings and Manufactured Homes 903.3.1.3, 903.3.5.1.1"
(12) In IBC, Chapter 35, NFPA referenced standard 13R-07 is deleted and replaced with the following:
"Number Title Referenced in code section number
13R-10 Installation of Sprinkler Systems in Residential Occupancies Up to and Including Four Stories in Height 903.3.1.2, 903.3.5.1.1, 903.3.5.1.2, 903.4"
(13) In IBC, Chapter 35, NFPA referenced standard 14-07 is deleted and replaced with the following:
"Number Title Referenced in code section number
14-10 Installation of Standpipe and Hose System 905.2, 905.3.4, 905.6.2, 905.8"
(14) In IBC, Chapter 35, NFPA referenced standard 17-02 is deleted and replaced with the following:
"Number Title Referenced in code section number
17-09 Dry chemical Extinguishing Systems 904.5, 904.11"
(15) In IBC, Chapter 35, NFPA referenced standard 17A-02 is deleted and replaced with the following:
"Number Title Referenced in code section number
17A-09 Wet Chemical Extinguishing System 904.5, 904.11"
(16) In IBC, Chapter 35, NFPA referenced standard 20-07 is deleted and replaced with the following:
"Number Title Referenced in code section number
20-10 Installation of Stationary Pumps for Fire Protection 913.1, 913.2.1, 913.5"
(17) In IBC, Chapter 35, NFPA referenced standard 72-07 is deleted and replaced with the following:
"Number Title Referenced in code section number
72-10 National Fire Alarm Code 901.6, 903.4.1, 904.3.5, 907.2, 907.2.5, 907.2.11, 907.2.13.2, 907.3, 907.3.3, 907.3.4, 907.5.2.1.2, 907.5.3.3, 907.6, 907.6.1, 907.6.5, 907.7, 907.7.1, 907.7.2, 911.1.5, 3006.5, 3007.6"
(18) In IBC, Chapter 35, NFPA referenced standard 92B-05 is deleted and replaced with

the following:

"Number Title Referenced in code section number
92B-09 Smoke Management Systems in Malls, Atria and Large Spaces 909.8"
(19) In IBC, Chapter 35, NFPA referenced standard 101-06 is deleted and replaced with the following:
"Number Title Referenced in code section number
101-09 Line Safety Code 1028.6.2"
(20) In IBC, Chapter 35, NFPA referenced standard 110-05 is deleted and replaced with the following:
"Number Title Referenced in code section number
110-10 Emergency and Standby Power Systems 2702.1"


Disclaimer: These codes may not be the most recent version. Utah may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.