Section Text (a) Intervals for cutoff switches

Trolley wires and trolley feeder wires shall be provided with cutout switches at intervals of not more than 2,000 feet and near the beginning of all branch lines.

(b) Overcurrent protection devices

Trolley wires and trolley feeder wires shall be provided with overcurrent protection.

(c) Location of wires

Trolley wires and trolley feeder wires, high-voltage cables and transformers shall not be located inby the last open crosscut and shall be kept at least 150 feet from pillar workings.

(d) Adequate insulation and guard devices; promulgation of safety guidelines

Trolley wires, trolley feeder wires, and bare signal wires shall be insulated adequately where they pass through doors and stoppings, and where they cross other power wires and cables. Trolley wires and trolley feeder wires shall be guarded adequately (1) at all points where men are required to work or pass regularly under the wires; (2) on both sides of all doors and stoppings; and (3) at man-trip stations. The Secretary or his authorized representatives shall specify other conditions where trolley wires and trolley feeder wires shall be adequately protected to prevent contact by any person, or shall require the use of improved methods to prevent such contact. Temporary guards shall be provided where trackmen and other persons work in proximity to trolley wires and trolley feeder wires.

Source Credit

(Pub. L. 91–173, title III, §310, Dec. 30, 1969, 83 Stat. 783.)


Editorial Notes STATUTORY NOTES AND RELATED SUBSIDIARIES EFFECTIVE DATE

Section operative 90 days after Dec. 30, 1969, except to the extent an earlier date is specifically provided for in Pub. L. 91–173, see section 509 of Pub. L. 91–173, set out as a note under section 801 of this title.

Publication Title United States Code, 2018 Edition, Supplement 2, Title 30 - MINERAL LANDS AND MINING
Category Bills and Statutes
Collection United States Code
SuDoc Class Number Y 1.2/5:
Contained Within Title 30 - MINERAL LANDS AND MINING
CHAPTER 22 - MINE SAFETY AND HEALTH
SUBCHAPTER III - INTERIM MANDATORY SAFETY STANDARDS FOR UNDERGROUND COAL MINES
Sec. 870 - Trolley wires and trolley feeder wires
Contains section 870
Date 2020
Laws In Effect As Of Date January 13, 2021
Positive Law No
Disposition standard
Statutes at Large References 83 Stat. 783
Public Law References Public Law 91-173
Disclaimer: These codes may not be the most recent version. United States may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.