View Our Newest Version Here

2012 South Carolina Code of Laws
Title 5 - Municipal Corporations
Chapter 25 - BUILDING CODES AND FIRE PREVENTION
Section 5-25-640 - Business buildings required to have standpipes; free connections and service with city water mains.


SC Code § 5-25-640 (2012) What's This?

All business buildings erected after February 20 1917 being more than fifty-six feet high and covering an area of more than five thousand superficial feet and also all buildings exceeding eighty feet in height shall have a four-inch or larger metallic standpipe within or near the front wall, extending above the roof and arranged so that engine hose can be attached from the street, such riser to have a two-and-one-half-inch hose coupling on each floor. The inspector may, with the approval of the State Fire Marshal, allow two or more standpipes of smaller size and proper hose couplings, provided they are of such sizes and number as to be at least equivalent in service to the large standpipe required. All hose couplings shall conform to the size and pattern adopted by the fire department. Free connection and service with the city water mains shall be furnished by the municipal authorities.

HISTORY: 1962 Code Section 47-1230; 1952 Code Section 47-1230; 1942 Code Section 7500; 1932 Code Section 7500; Civ. C. '22 Section 4615; 1917 (30) 77; 1960 (51) 1646.

Disclaimer: These codes may not be the most recent version. South Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.