2006 New York Code - Piping From Siamese Connection.



 
    §  27-960  Piping  from  siamese  connection.  Piping from the siamese
  connection shall be the same size as the riser or trunk main to which it
  is connected, except that it need  not  be  more  than  five  inches  in
  diameter  when  supplying larger riser or feed mains. When more than one
  siamese connection is required, the piping from each siamese  connection
  need not exceed four inches in diameter.

Disclaimer: These codes may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.