    §   27-811   Insulation   materials.   All  insulations  shall  be  of
  noncombustible materials. All coverings, vapor  barriers  and  adhesives
  shall  have a flame spread rating no higher than twenty-five and a smoke
  developed rating no higher than fifty.  Adhesives  and  mastic  finishes
  shall be tested in sufficient bulk to produce maximum burning, and shall
  be tested in accordance with reference standard RS 14-11.

Disclaimer: These codes may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.