There is a newer version of the New York Consolidated Laws
2006 New York Code - Partition Loads.
§ 27-555 Partition loads. Weights of all partitions shall be considered, using either actual weights at locations shown on the plans or the equivalent uniform load given in subdivision (b) of this section. (a) Actual loads. Where actual partition weights are used, the uniform design live load may be omitted from the strip of floor area under each partition. (b) Equivalent uniform load. The equivalent uniform partition loads in reference standard RS 9-1 may be used in lieu of actual partition weights except for bearing partitions or partitions in toilet room areas (other than in one- and two-family dwellings), at stairs and elevators, and similar areas where partitions are concentrated. In such cases, actual partition weights shall be used in design. Except as otherwise exempted, equivalent uniform loads shall be used in areas where partitions are not definitely located on the plans, or in areas where partitions are subject to rearrangement or location.
Disclaimer: These codes may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.