2006 Indiana Code - CHAPTER 5. INSTALLATION OF UNDERGROUND STORAGE TANKS

IC 13-23-5
     Chapter 5. Installation of Underground Storage Tanks

IC 13-23-5-1
Restrictions on time
     Sec. 1. Subject to section 2 of this chapter, an underground storage tank, whether of single or double wall construction, may not be installed before the effective date of the rules adopted under IC 13-23-1-2 for the purpose of storing regulated substances unless:
        (1) the tank will prevent releases due to corrosion or structural failure for the operational life of the tank;
        (2) the tank is:
            (A) cathodically protected against corrosion;
            (B) constructed of noncorrosive material;
            (C) steel clad with a noncorrosive material; or
            (D) designed to prevent the release or threatened release of any stored substance; and
        (3) the material used in the construction or lining of the tank is compatible with the substance to be stored.
As added by P.L.1-1996, SEC.13.

IC 13-23-5-2
Restrictions based on soil resistivity
     Sec. 2. If soil tests conducted in accordance with:
        (1) ASTM Standard G57-78; or
        (2) another standard approved by the commissioner as exhibiting the same or a greater degree of reliability and accuracy;
show that soil resistivity in an installation location is at least twelve thousand ohms per centimeter (12,000 ohm/cm), a storage tank without corrosion protection may be installed in that location during the period referred to in section 1 of this chapter.
As added by P.L.1-1996, SEC.13.

Disclaimer: These codes may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.