2005 Connecticut Code - Sec. 29-237. (Formerly Sec. 19-434). Inspection.
Sec. 29-237. (Formerly Sec. 19-434). Inspection. All boilers included under this
chapter shall be inspected by a state boiler inspector or by a special inspector employed
by an insurance company licensed to insure boilers in this state as follows:
(2) Power boilers that operate with internal water treatment under the direct supervision of a qualified engineer shall be inspected every eighteen months. Such boiler inspection shall consist of (A) a thorough internal and external inspection while not under pressure and (B) an external inspection under operating conditions not more than nine months after the internal and external inspection.
(3) Where construction will permit, low pressure steam or vapor heating boilers, hot water heating boilers, hot water supply boilers and hot water heaters shall be inspected externally biennially and internally at the discretion of the boiler inspector. If a boiler inspector decides a hydrostatic test is necessary to determine the safety of a boiler or heater, such test shall be made under the inspector's direction. The Commissioner of Public Safety may order inspections by the Department of Public Safety or the insurance carrier in addition to the regular annual or biennial inspections to clear up any doubts as to the safety of continuing the operation of any boiler or heater included in this chapter, but no additional fee shall be charged or allowed for such additional inspections, unless the owner or user is found to have operated or ordered or permitted the operation of such boiler or heater, intentionally or negligently, in violation of this chapter or the boiler regulations. Each boiler insurance carrier shall forward to the commissioner, within thirty days following each inspection as required by this chapter, a report of such inspection upon appropriate forms as promulgated by the commissioner, who may use the form suggested by the American Society of Mechanical Engineers.
(1949 Rev., S. 4739; 1953, S. 2370d; 1963, P.A. 161; P.A. 77-614, S. 507, 610; P.A. 85-6; P.A. 86-83, S. 5; P.A. 99-138, S. 1.)
History: 1963 act added that yearly inspection shall apply only to power boilers, lowering time lapse between internal inspections and external inspections under pressure from fifteen to fourteen months, added provisions re biennial inspection of certain boilers and changed technical language; P.A. 77-614 replaced labor commissioner and department with commissioner and department of public safety in Subsec. (b), effective January 1, 1979; Sec. 19-434 transferred to Sec. 29-237 in 1983; P.A. 85-6 amended Subsec. (b), providing that low pressure steam or vapor heating boilers, hot water heating and supply boilers be inspected internally at the boiler inspector's discretion, where previously both internal and external inspections were required "where construction will permit"; P.A. 86-83 amended Subsec. (b) to require inspection of hot water heaters; P.A. 99-138 redesignated former Subsec. (a) as Subdiv. (1), added Subdiv. (2) re provisions for inspection of boilers that operate with internal water treatment under the supervision of an engineer and redesignated former Subsec. (b) as Subdiv. (3).
Disclaimer: These codes may not be the most recent version. Connecticut may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.