§ 27-941 Cross connections. (a) Standpipe systems that include more
than one riser shall have all risers cross-connected at, or below, the
street entrance floor level, except as otherwise provided in this
section.
(b) Standpipe systems in buildings required by the provisions of
section 27-943 of this article to have one or more zones shall be so
designed and installed that the risers supplied from each zone will be
cross-connected below, or in, the story of the lowest hose outlets from
the water source in each zone. Horizontal intermediate check valves
shall be installed in the run of each riser continuing into a higher
zone in such manner as to permit all upper zones of the system to be fed
through one riser from the zone below and to prevent any lower zone of
the system from being supplied from a zone above.
(c) Risers supplied by an upper level cross connection shall be
provided with manual control valves or remote control valves, so
arranged that risers supplied by the upper level cross connections may
independently be shut off from the tank supplies.
(d) Cross connections shall be at least as large as the largest riser
supplied by the cross connection. However, when supplying two, but not
more than four four-inch risers, the cross connection shall not be less
than five inches. The cross connection shall not be less than six inches
for all other riser combinations.
(e) Where there is no cellar, cross connections may be hung from the
ceiling of the lowest story.
(f) Each siamese connection shall be connected to a riser or to a
cross connection connecting other siamese hose connections or risers.
The pipe from the siamese connection to the riser or cross connection
shall be five inch i.p.s., except that a four inch pipe shall be
sufficient when such pipe supplies a single four inch riser system. The
pipe from the siamese connection shall be run as directly as practicable
to the riser or cross connection.