2006 New York Code - Required Sprinklers.



 
    §  27-954  Required sprinklers. A system of automatic sprinklers shall
  be provided in the areas listed in  this  section  and  as  required  in
  subchapters  four  through eight of this chapter. A summary of sprinkler
  requirements is given in table 17-2.
    (For Table 17-2 see chapter 839 of the laws of 1986)
 
    (a) Buildings classified in high hazard occupancy group A.
    (b) Spaces classified in high hazard occupancy group A.
    (c) Buildings classified in storage occupancy group B-1 exceeding  one
  thousand  square  feet  in  floor  area, or seventy-five feet or more in
  height, except as modified under subdivisions a,  b  and  c  of  section
  27-455 of article ten of subchapter seven of this code.
    (d)  Spaces  classified  in storage occupancy group B-1 exceeding five
  hundred square feet in floor area, except as modified under subdivisions
  a, b and c of section 27-455 of article ten of subchapter seven of  this
  code.
    (1)  Such  storage  spaces  less than five hundred square feet in area
  shall install a system of automatic sprinklers,  when  required  by  the
  commissioner or the fire commissioner.
    (e)  Buildings  and  spaces  classified in storage occupancy group B-2
  exceeding five thousand square feet in floor area, or seventy-five  feet
  or  more  in height, except as modified under subdivisions a, b and c of
  section 27-455 of article ten of subchapter seven of this code.
    (f) Spaces in high rise buildings classified in  mercantile  occupancy
  group  C,  spaces  classified  in mercantile occupancy group C exceeding
  seventy-five hundred square feet in floor area  or  with  an  unenclosed
  stair or escalator between any two or more floors.
    (g) Buildings classified in industrial occupancy group D when required
  by section two hundred eighty of the labor law or when seventy-five feet
  or more in height.
    (h)  Spaces  classified  in  industrial  occupancy group D-1 exceeding
  seventy-five hundred square feet, in floor area excluding heliports.
    (i) Buildings classified in occupancy group E,  one  hundred  feet  or
  more  in  height  having  air-conditioning and/or mechanical ventilation
  systems that serve more  than  the  floor  in  which  the  equipment  is
  located,   and   on  or  before  January  eighteenth,  nineteen  hundred
  seventy-six, in existing office buildings one hundred feet  or  more  in
  height  having  such  systems,  showroom  spaces  exceeding seventy-five
  hundred square feet in area located more  than  forty  feet  above  curb
  level.  The  sprinkler  system  may  be  connected to the domestic water
  supply and/or the standpipe risers.   Where  connected  to  a  standpipe
  riser,  provision  shall  be  made  to prevent excessive pressure on the
  sprinkler heads. If such  work  is  not  completed  on  or  before  July
  eighteenth,  nineteen  hundred  seventy-four,  the  owner shall submit a
  statement to the commissioner, with a copy  to  the  fire  commissioner,
  setting  forth  a plan and time schedule for the performance of the work
  and completion within the prescribed time. Such plan and schedule  shall
  be  subject  to the approval of the commissioner. Failure to comply with
  the provisions of this subdivision, or to perform the work in accordance
  with  the  time  schedule,  as  approved  by  the  commissioner,   shall
  constitute a violation.
    (j)  Dressing  rooms  and  property rooms used in conjunction with all
  places of assembly, except for F-1B places  of  assembly  not  providing
  live entertainment.
    (k)   Corridors  and  exit  passageways  of  buildings  classified  in
  institutional occupancy group H where the building or  building  section
  is  not  otherwise  required  to  be  fully  sprinklered  as provided in
  subchapter four. Patient rooms in H-2  occupancies  shall  be  protected

with smoke detectors complying with provisions of section 27-955 of this article when not required to be sprinklered by the provisions of subchapters four through seven. (l) Regardless of occupancy group classification, any story above grade that cannot be ventilated by at least twenty square feet of free openable area and the first story below grade when it cannot be ventilated by at least thirty-five square feet of openable area per ten thousand cubic feet of volume. Such ventilation shall be provided by operable windows or other natural ventilation sources complying with section 27-749 of article six of subchapter twelve of this chapter. All other stories below grade shall be sprinklered. Sprinklers may be omitted in toilets, shower rooms, stairs, and mechanical and electrical equipment rooms. For purposes of this subdivision fixed windows may be considered as "openable" (may be broken inward) if they are not more than one hundred feet above grade, or fifteen feet below grade; or if they are located within six feet of an accessible roof or setback; or if they are located within six feet of an operable window having at least three foot by three foot openings. (1) Buildings classified in occupancy group J-2 with not more than three dwelling units and buildings classified in occupancy group J-3 shall be exempt from this provision provided all spaces classified in storage occupancy group B-2 exceeding one thousand square feet have been sprinklered in accordance with the requirements of this subchapter. (m) Rubbish chutes, laundry chutes, and chutes for similar uses. Sprinklers, protected from damage, shall be provided in accordance with reference standard RS 17-2, RS 17-2A, or RS 17-2B, as applicable. (n) Soiled linen collection and sorting areas. (o) Workshops exceeding one hundred square feet except in one- and two-family dwellings. (p) Refuse collection and disposal areas. (q) Drying area of laundries or similar spaces in which two or more clothes drying machines are installed. Sprinklers to be spaced to cover area five feet in front, rear, and sides of machines. (r) Sprinklers for cooling towers, where required by subchapter five of this chapter, shall be either a dry pipe or deluge system designed in accordance with the provisions of reference standard RS 17-4. (s) (1) F-4 places of assembly used as cabarets. (2) Stages within F-1a, F-1b, F-3 or F-4 occupancies providing live entertainment at anytime as set forth in subchapter eight of this chapter. (t) Buildings classified in occupancy group J-1, buildings classified in occupancy group J-2 with four or more dwelling units, spaces classified in occupancy group J-1, and spaces classified in occupancy group J-2 with four or more dwelling units. (u) Places of assembly located within a building classified in occupancy group J-1. (v) Catering establishments and banquet halls with an occupant load of three hundred or more persons. (w) In all existing buildings classified in occupancy group J-1 (except for "residential hotels," as such term is defined by the commissioner pursuant to rules,) all spaces listed in subdivisions (c), (d), (l), (m), (n), (o), (p) and (q) of this section, except that an approved smoke detection alarm system may be installed in those locations described under subdivisions (o) and (q) in lieu of sprinklers other than in those locations where sprinklers are required pursuant to section 27-123.2 of this chapter. Such smoke detection system shall be of the supervisory type connected to an approved central station.
(x) High rise buildings classified in occupancy group F-1, F-3, F-4, or G, or any spaces classified in such occupancy groups located within a high rise building or building section more than seventy-five feet above curb level. (y) Spaces in existing high rise buildings classified in occupancy group C and any space in an existing building classified in occupancy group C with an unenclosed stair or escalator between any two or more floors. (z) Notwithstanding the provisions of subdivision i of this section, high rise buildings classified in occupancy group E and low rise buildings classified in occupancy group E with a total gross floor area of one hundred thousand square feet or more. (aa) Regardless of occupancy group classification, in each basement, cellar or other location below grade, regardless of the floor area of such space, in any mercantile establishment in which the fire commissioner permits the storage of flammable or combustible mixtures pursuant to sections 27-4066, 27-4070 or 27-4094 of this code, except that, where such flammable or combustible mixtures are stored in such basement, cellar or other location below grade, in a room or other area that is segregated, vertically and horizontally, from surrounding spaces by a fire separation of not less than a two-hour fire-resistance rating, such system of automatic sprinklers shall be required only within such room or other area. Such system of automatic sprinklers shall conform to the requirements for automatic sprinklers for spaces classified in storage occupancy group B-1 pursuant to subdivision d of this section.

Disclaimer: These codes may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.