2006 New York Code - Chimneys For Industrial Or Municipal Incinerator Plants.
§ 27-877 Chimneys for industrial or municipal incinerator plants. Chimneys for central incinerator plants shall be constructed in accordance with the requirements for: (a) Medium temperature chimneys if the incinerator is provided with a heat recovery unit or other means to assure a flue gas temperature not in excess of one thousand degrees Fahrenheit at the base of the stack. (b) High temperature chimneys if the incinerator has no heat recovery unit or other means to assure a flue gas temperature less than one thousand degrees Fahrenheit.
Disclaimer: These codes may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.