2006 New York Code - Corridors.



 
    §  27-761  Corridors.  Unless  natural  sources complying with section
  27-749 of article six of this subchapter provides  ventilating  openings
  equivalent  to  at  least  two  and  one-half percent of the floor area,
  corridors in buildings of occupancy groups H-1, J-1 and  J-2  more  than
  three  stories  in  height, shall be mechanically ventilated by a system
  supplying at least one-half cubic foot of outdoor  air  per  minute  per
  square  foot of floor area. When air conditioned, a part of the required
  supply may be recirculated as  equivalent  outdoor  air,  but  at  least
  thirty-three  and  one-third percent of the required air supply shall be
  actual outdoor air.

Disclaimer: These codes may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.