2006 New York Code - Bearing Capacity Of Nominally Unsatisfactory Bearing Materials.



 
    §   27-679   Bearing  capacity  of  nominally  unsatisfactory  bearing
  materials.    Whenever  soils  exploration  shows  that   the   proposed
  foundation  would  rest on, or be underlain by, nominally unsatisfactory
  bearing materials, a report based on soil tests and foundation  analysis
  (including  analysis  of  undisturbed  samples) shall be submitted by an
  architect or engineer, demonstrating, subject to  the  approval  of  the
  commissioner,  that  the proposed construction, under a condition of one
  hundred  percent  over  load,  is  safe  against  failure  of  the  soil
  materials.  The report shall also show that the probable total magnitude
  and distribution of settlement to be expected  under  design  conditions
  will  not  result  in  instability  of  the  building or stresses in the
  structure in excess of the allowable values  established  in  subchapter
  ten of this chapter. In addition, the following provisions shall apply:
    (a) Fill materials.
    (1)  CONTROLLED  FILLS.  Fills  shall  be  considered  as satisfactory
  bearing materials of class 6-65 or 7-65 when placed in  accordance  with
  the   following   procedures,   under   the  provisions  for  controlled
  inspection.
    a. Before placement of fill, the  existing  ground  surface  shall  be
  stripped  of  all  organic  growth,  timber,  rubbish, and debris. After
  stripping, the ground surface shall  be  compacted  to  the  density  in
  subparagraph d of this paragraph.
    b.  Materials  for  fill shall consist of sand, gravel, crushed stone,
  crushed gravel, or a mixture of these,  and  shall  contain  no  organic
  matter.  The  fill  materials  shall contain no particles exceeding four
  inches in the largest dimension. No more than thirty  per  cent  of  the
  material  shall  be retained on a three-quarter inch sieve. The material
  passing the three quarter inch sieve shall contain, by weight,  no  more
  than  forty  percent  passing  the  one hundred sieve, or twelve percent
  passing the two hundred sieve.
    c. The grading of the fill shall be determined in accordance with  the
  applicable procedures of reference standards RS 11-1 and RS 11-2.
    d. Fill shall be placed and compacted at its optimum moisture content,
  in  uniform  layers not more than twelve inches thick (after compaction)
  and each layer shall be thoroughly compacted to a density not less  than
  ninety-five  percent  of the density prescribed in reference standard RS
  11-3. The field density shall be verified by in-place density tests made
  on each lift of the embankment. Fill shall not be placed when frozen  or
  placed on a frozen or wet sub-grade.
    (2) UNCONTROLLED FILLS. Fill material, other than controlled fill, may
  be  used  for  the  support of buildings, other than one- and two-family
  dwellings, and may be considered as  satisfactory  bearing  material  of
  applicable class, subject to the following:
    a.  The  soil  within  the  building area shall be explored using test
  pits.  At least one test pit, penetrating at least eight feet below  the
  level  of  the  bottom  of  the proposed footings, shall be provided for
  every twenty-five hundred square feet of building area. Where such  test
  pits consistently indicate that the fill is composed of material that is
  free of voids and free of extensive inclusions of mud, organic materials
  such  as  paper,  garbage,  cans,  or  metallic objects, and debris, the
  provisions of subparagraphs b and c of this paragraph shall apply. Where
  the test pits show such voids or inclusions, the  additional  provisions
  of  subparagraph d of this paragraph shall apply. Borings may be used in
  lieu of test pits, provided that continuous samples at least four inches
  in diameter are recovered.
    b. The building area shall be additionally explored using one standard
  boring under each column. These borings shall  be  carried  to  a  depth
  sufficient  to  penetrate  into natural ground, but not less than twenty

feet below grade, and a sufficient number shall penetrate deeper than twenty feet as required to meet the provisions of section 27-663 of article two of this subchapter. Where such borings show voids or inclusions, the provisions of subparagraph d of this paragraph shall apply. c. The allowable soil bearing pressure on the fill material shall not exceed two tons per square foot. d. Wherever the fill shows voids or inclusions as described in subparagraphs a and b of this paragraph either the fill shall be treated as having no presumptive bearing capacity, or the building shall incorporate adequate strength and stiffness to bridge such voids or inclusions or shall be articulated to prevent damage due to differential or localized settlement of the fill. (b) Organic silts, organic clays, soft inorganic clay, loose inorganic silt, and varved silt. (1) The allowable bearing pressure shall be determined independently of table 11-2 subject to the following: a. For varved silts, the soil bearing pressure produced by the proposed building shall not exceed two tons per square foot, except that for desiccated or preconsolidated soils, higher bearing pressures will be allowed. b. For organic silts or clays (groups OL and OH) or for soft or loose soils of groups ML, CL, MH, and CH, the soil bearing pressure produced by the proposed building shall not exceed one ton per square foot except that a value of two tons per square foot will be permitted on soils that are adequately preconsolidated or artificially treated. (2) The report required in this section shall contain, as a minimum, the following information: a. Geological profiles through the area defining the stratigraphy. b. Sufficient laboratory test data on the compressible material to indicate the coefficient of consolidation, coefficient of compressibility, permeability, secondary compression characteristics, and Atterberg limits. c. Where the design contemplates improvement of the natural bearing capacity and/or reduction in settlements by virtue of preloading, cross sections showing the amount of fill and surcharge to be placed on design details showing the required time for surcharging shall be indicated, and computations showing the amount of settlement to be expected during surcharging. Records of settlement plate elevations and pore pressure readings, before, during, and after surcharging, shall be filed with the commissioner. d. The estimated amount and rate of settlement expected to occur after the structure has been completed, including the influence of dead and live loads of the structure. e. A detailed analysis showing that the anticipated future settlement will not adversely affect the performance of the structure. f. Where sand drains are to be used, computations showing the diameter, spacing, and method of installation of such drains, shall be provided. (c) Artificially treated soils. Nominally unsatisfactory soil materials that are artificially compacted, cemented, or preconsolidated (including soils compacted by vibration, cemented by chemical injection, or preconsolidated by use of electric current, but not including cases where preconsolidation consists solely of the use of surcharge with or without sand drains) may be used for the support of buildings, and nominally satisfactory soil materials that are similarly treated may be used to resist soil bearing pressures in excess of those indicated in table 11-2 for the soil in its natural state, subject to the following:
(1) The vertical and lateral extent of the soil that is compacted, cemented, or preconsolidated shall conform to the full extent of the distribution of loading that is assumed for purposes of computing the intensities of the soil bearing pressure. The actual soil bearing pressure shall not exceed the limitations of subdivisions (a) and (b) of this section for nominally unsatisfactory bearing materials or, for satisfactory bearing materials, shall not exceed the limitations of table 11-2. (2) After the treatment procedure, a minimum of one boring shall be made for every sixteen hundred square feet of that portion of the building area that is supported on treated soil, and a sufficient number of samples shall be recovered from the treated soil to demonstrate the efficacy of the treatment.

Disclaimer: These codes may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.