§ 27-437 Fire protection. Heliports shall be provided with fire-foam extinguishing equipment and fire alarm facilities meeting the following requirements: (a) At least two hose stations housing approved foam generating equipment shall be provided remote from each other and located adjacent to outlets of the building standpipe system or other source of water supply. Hoses shall be provided with nozzles and related equipment for dispensing foam to all portions of the roof. (b) The building standpipe system or other source of water supply shall be capable at all times of providing two hose streams simultaneously, each of which will afford foam application at a total water rate of at least sixty gallons per minute at a nozzle presure of seventy-five psi for a period of ten minutes. (c) A fire alarm system meeting the installation requirements of subchapter seventeen of this chapter shall be provided with a direct connection to the central station of an operating fire alarm company and with a local alarm to all heliport personnel.
Disclaimer: These codes may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.