2006 New York Code - General Provisions Applying To All Buildings.



 
    §   27-4205   General   provisions   applying  to  all  buildings.  a.
  Construction.  1. All rooms in which flammable motion  picture  film  is
  handled  or  stored  shall  be  separated from each other and from other
  parts of  the  building  by  partitions  constructed  as  specified  for
  partitions in buildings of fireproof construction in sections 27-340 and
  27-346  of  the  code,  except  that partitions employing metal, wood or
  glass are prohibited. Such rooms shall be used for no other purposes.
    2. Every room in which flammable motion picture film is handled and in
  which more than two people work shall have two or more exits remote from
  each other. All doors in such rooms shall be fireproof and self  closing
  and  shall open outwardly. Artificial lighting shall be only by electric
  lights, having air-tight bulbs or globes,  or  fitted  with  vapor-proof
  marine type fixtures which are stationary, rigid and fitted with keyless
  sockets.
    3.  Every  room containing over one hundred thousand feet of flammable
  motion picture film and in which film was not handled or stored  on  the
  second  day  of June, nineteen hundred thirty-one shall be provided with
  vents which will open automatically in case of fire. These shall  be  of
  ample  size  and  may be in the form of automatic skylights or automatic
  opening window sashes.
    4. It shall be unlawful to handle or store   flammable motion  picture
  film  in any cellar, or in any basement unless such basement is directly
  ventilated to the outer air and is  provided  with  a  means  of  egress
  directly to the street.
    b.  Fittings.  In every room where  flammable motion picture films are
  repaired or pieced together, used, handled or stored, all furniture  and
  fittings  shall  be  of  metal  or other fireproof material, except that
  chair seats and table  and  floor  coverings  may  be  of  slow  burning
  material,  and  Joining,  assembling  and  inspection tables shall be at
  least four inches distant from any radiator or heating apparatus.
    c. Number of persons permitted in a room. In all rooms, except  motion
  picture  studios,  in which  flammable motion picture films are handled,
  the ratio of square feet of floor area to the number  of  persons  shall
  not  be  less  than  thirty-five  square  feet  per  person.  Except  as
  hereinafter provided, not more than fifteen persons shall  work  in  one
  room at the same time.
    d. Film in containers. All  flammable motion picture film not actually
  being  worked  upon  or  going  through  some operation shall be kept in
  closed containers. All flammable motion picture film not  necessary  for
  immediate  use  shall  be  kept  in  approval  vaults  or  cabinets, and
  flammable motion picture film stored in vaults shall be  kept  on  racks
  and  shall  not  be  stored  or kept on the floor of vaults at any time;
  except that in vaults designed for shipping  rooms  there  shall  be  no
  prohibition  against storing or keeping flammable motion picture film on
  the floor of such vaults in shipping containers.
    e. Receptacles for waste. 1. Waste, scraps, shavings, cuttings,  short
  lengths  or other waste materials of flammable motion picture film shall
  be kept under water  in  standard  metal  waste  cans  from  which  such
  materials shall be removed at least twice daily. It shall be unlawful to
  keep other waste or rubbish in these cans.
    2.  Removal of  flammable motion picture film waste materials shall be
  made in  closed  containers  as  defined  in  section  27-4202  and  the
  containers  for  flammable  motion picture film shall contain sufficient
  water at all times so that the waste materials in the  containers  shall
  be entirely submerged.
    3.  The  metal  containers  shall  be kept in a room used for no other
  purpose and not more than ten such  containers  shall  be  kept  in  any
  building.  Junk  flammable  motion  picture film shall be kept in closed

receptacles and stored in approved vaults. Flammable motion picture film shall not be baled or burned within the building. f. Storage of cements. No collodion, amyl acetate or other similar flammable cement or liquid in quantities greater than one quart shall be kept in a room where flammable motion picture films are stored or repaired. g. Fire extinguishing appliances. Premises wherein flammable motion picture films are stored, repaired or examined shall be equipped with a number of sand and water buckets and fire extinguishers satisfactory to the commissioner. Each room, other than a vault, in which flammable motion picture film is handled or stored, shall be equipped with at least one approved two and one-half gallon chemical extinguisher and one pail of water. h. Heating. Artificial heating in any building or room other than a vault or cabinet, in which flammable motion picture film is used, handled or stored, shall be restricted to steam not exceeding ten pounds pressure or hot water; provided, however, that this shall not be construed as prohibiting the installation of an indirect system employing high pressure steam when the radiators or heating coils of such system are not located in the room or rooms to be heated. Heat generating apparatus must be in a separate room. All steam pipes within six feet of the floor, and where passing through partitions or racks or near woodwork, shall be covered with approved pipe covering. All radiators, heating coils, pipes and returns that are near the floor or are so located as to permit any combustible material, waste or dirt to come in contact therewith shall be guarded and protected by means of one-fourth inch mesh galvanized steel wire cloth No. 20 B.& S. gauge, or by its equivalent, approved by the commissioner. The bottoms of such guards shall be arranged so as to lift up for cleaning purposes, and the tops shall slope so that guards cannot be used as shelves. i. Projecting machines. Not more than five projecting machines shall be located in one room where flammable motion picture film is projected. j. Cleaning, polishing and buffing. Cleaning, polishing and buffing machines shall not be located in rooms with other operations connected with flammable motion picture film. Not more than eight standard or sixteen sub-standard reels of flammable motion picture film shall be on hand in such room at any one time. k. Soldering. Soldering of cases when done in the building shall be conducted in a room used for no other purposes. Walls shall be constructed of six inch hollow tile plastered on each side to a thickness of one-fourth inch or by its equivalent. The area of the room shall not exceed sixty square feet. The opening to the room shall not be from another film handling room, and shall be protected by a self-closing fire door. An automatic vent shall be provided with a ratio of seventy square inches for each five hundred pounds of flammable motion picture film. The room shall be equipped with automatic sprinklers with a ratio of one sprinkler for each fifteen square feet with proper sheet metal baffles. The quantity of flammable motion picture film in the room shall not exceed one case. A sheet of hard asbestos at least one-eighth inch in thickness shall be provided inside of containers to be soldered, and such asbestos sheet shall be arranged so as completely to separate the flammable motion picture film from the lid or cover of the container. l. Spraying. Spraying flammable motion picture film with a flammable liquid shall be done in a room containing no other process and with an exhaust fan of sufficient capacity to remove all vapors as formed. It
shall be unlawful to keep more than five gallons of flammable liquid in approved containers in this room. m. Silver reclaiming from flammable motion picture film. Silver reclaiming from flammable motion picture film shall not be conducted in the laboratory building unless in a section cut off by a standard fire wall. Flammable motion picture film before and after processing shall be kept in containers in vaults. Removal of flammable motion picture film from spools and processing shall be in a room entirely cut off from the vault area. n. Vaults for storing flammable motion picture film. 1. Vaults must be constructed in accordance with plans submitted to and approved by the commissioner. 2. Vaults shall not exceed seven hundred fifty cubic feet in inside dimensions, except that the shipping room vaults shall not exceed one hundred fifty square feet in area and fifteen hundred cubic feet in inside dimensions. 3. Walls and floors shall be constructed of not less than eight inches of brick, six inches of reinforced concrete or of twelve inches of hollow tile plastered on both sides to a thickness of at least one-fourth inch, except that walls of shipping room vaults may be constructed with not less than four inches of terra cotta, brick or concrete. Walls and floors shall be without cracks or holes permitting escape of gases of combustion into the building. 4. The roof shall be a reinforced concrete roof at least six inches thick. Where the floor above the vault or the roof of the building is equivalent to this, it may serve as the vault roof, and a heavy metal screen or its equivalent may be installed below the required roof to limit the interior vault space to the required number of cubic feet. 5. Unless the building is designed to sustain safely the load resulting from the vault being filled with water, the vault shall be provided with suitable drains or scuppers to the outside of the building. 6. Proximity to stacks and other sources of heat must be avoided. 7. Door openings shall be protected with two fire doors, one on each face of the wall. The interior door shall be automatic and the outer door shall be of the swinging type and shall close into a rabbet, or shall otherwise be made tight to prevent the passage of flame around the edges. The outer door shall be self-closing and if fastened open, shall be arranged to close automatically in case of fire originating in or out of the vault. 8. Each vault shall be provided with an independent vent having a minimum effective sectional area of fourteen square inches per one hundred pounds of film capacity. The vent area for a vault of seven hundred fifty cubic feet shall be fourteen hundred square inches. 9. Vent flues inside the building shall be constructed of five inches of reinforced concrete or of a construction equivalent to that required for smoke chimneys, except that vents for shipping room vaults shall be not less than No. 18 U.S. gauge galvanized steel or its equivalent, covered with one inch of asbestos. The outlet of each vent shall be above the roof or made to face the street, court or other clear opening, giving a distance of at least fifty feet to any window or other opening exposed thereby and not in the same plane, and giving a distance of at least twenty-five feet to any fire escape on the same or higher level. 10. Each vent shall be protected against the weather by single thickness glass one-sixteenth of an inch thick, painted a dark color, in a sash arranged to open automatically in case of fire by means of an approved releasing device placed inside the vault. The area of the glass shall be the effective sectional area of the vent opening. No pane of
glass shall be smaller than two hundred square inches. Any protection equivalent to that specified in this paragraph may be accepted in lieu thereof. 11. A light wire screen not coarser than one-eighth inch mesh shall be placed over each vent. Bars or screens designed to prevent burglary or injury to contents shall not have a mesh of less than four inches and shall give a net opening equal to that called for under the vent. Bars and screens shall be so arranged as not to interfere with the automatic operation of the sash. 12. Film vaults shall not be provided with skylights or glass windows other than as specified under vents. 13. Vaults shall be provided with racks of metal or other noncombustible material, except that in shipping room vaults racks shall not be required where flammable motion picture film is kept in closed containers. Vertical noncombustible partitions equivalent in durability and heat insulation to three-eighths inch hard asbestos and extending from the floor to the ceiling shall be provided to divide the racks into sections so that the amount of flammable motion picture film protected by each sprinkler shall not exceed eight hundred thirty pounds. Racks shall not obstruct vent openings. 14. Vaults shall be protected with automatic sprinklers, with a ratio of one head to each sixty-two and one-half cubic feet of total vault space. A vault of seven hundred fifty cubic feet shall have twelve sprinkler heads. Sprinkler heads shall be arranged to give uniform distribution within the sections formed by the above mentioned partitions. They shall be separated by sheet-metal baffles extending below the sprinkler head. 15. All lights shall be at the ceiling and of the fixed marine type with vapor-proof globes and conduit wiring. All switches shall be outside the vault. 16. Heating, when required to prevent sprinkler pipes from freezing, shall be by hot water or low pressure steam with automatic control limiting the vault temperature to not in excess of seventy degrees Fahrenheit. Radiators shall be placed at the ceiling, over aisle space, with pipes and radiators protected with wire guards so arranged that no flammable motion picture film can be placed within twelve inches of such pipes or radiators. 17. Materials other than film and film cement shall not be stored in the film vault. o. Cabinets for storing flammable motion picture film. 1. Cabinets shall be of a construction approved by the commissioner and shall not have a capacity in excess of thirty-eight standard or seventy-six sub-standard reels or three hundred eighty pounds of flammable motion picture film. 2. Cabinets may be constructed of one-fourth inch asbestos board on a framework of one and one-fourth by one and one-fourth by one and one-eighth inch angles or may be made of No. 18 U.S. gauge metal double walled with one and one-half inch air space. 3. Racks in the cabinet shall be of metal so arranged that containers can be stored on edge. 4. Doors shall be so arranged as to remain normally closed and shall be provided with catches at three points. 5. Cabinets having a capacity of over five standard or ten sub-standard reels or fifty pounds of flammable motion picture film shall be provided with a vent to the outside of the building. The vent shall have a minimum effective sectional area of fourteen square inches per hundred pounds of flammable motion picture film capacity.
6. Vent flues inside the building shall be of a construction equivalent to No. 18 U.S. gauge metal, covered with one inch of heat insulating material. 7. Each cabinet holding over five standard or ten sub-standard reels, or fifty pounds of flammable motion picture film, shall be provided with at least one automatic sprinkler, provided, however, that a cabinet constructed so that each reel is in a separate compartment and will burn out without communicating fire to film in an adjoining compartment, need not be provided with an automatic sprinkler. p. "No smoking" signs. Every room in which flammable motion picture film is handled shall have posted therein in conspicuous locations "no smoking" signs.

Disclaimer: These codes may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.