    §  27-369  Corridors.  Corridors  shall be kept readily accessible and
  unobstructed at all times. Corridors shall be kept free  of  combustible
  contents  except that in buildings classified in occupancy groups G, H-1
  and H-2, combustible contents may be stored  in  noncombustible  lockers
  and  combustible  bulletin  boards meeting the requirements of table 5-4
  shall be permitted.
    (a) Capacity. The capacity and minimum width of corridors shall be  as
  listed  in  table  6-1. Width shall be measured in the clear between the
  narrowest points produced by any projections such as radiators, lockers,
  drinking fountains, or room or locker  door  swings,  except  that  such
  width  may  be  reduced by projections up to eighteen inches wide to the
  extent of two inches per unit of exit width if the total  area  of  such
  projections  does  not  exceed  five per cent of the area of the wall on
  which they occur.
    (b) Height. Corridors shall have a clear  height  of  seven  feet  six
  inches  for  at  least  seventy-five per cent of the floor area, with no
  point less than seven feet in height. No projection  below  the  ceiling
  shall be located so as to obstruct full view of exit signs.
    (c)  Length.  Corridors  shall  be  subdivided  by  smoke barriers, as
  defined in subchapter two, into the following lengths:
    Educational occupancy group G....................300 ft.
    Institutional occupancy groups H-1 and H-2.......150 ft.
    Residential occupancy groups J-1 and J-2.........150 ft.
    Where smoke barriers are penetrated by  doors,  such  doors  shall  be
  smoke  stop  doors in conformance with subdivision (c) of section 27-371
  of this article.
    (d) Dead ends. Dead ends in corridors  shall  not  exceed  the  length
  listed  in  table  6-1,  except  that  in  all  occupancy  groups except
  occupancy  group  H,  when  a  corridor  is   completely   enclosed   in
  construction having a two hour fire-resistance rating, with all corridor
  doors  being self-closing and having a fire protection rating of one and
  one-half hours, the permissible length of dead ends may be increased one
  hundred per cent above the length listed in table 6-1. Dead end distance
  shall be measured from the centerline of the door opening nearest to the
  closed end of the corridor to the center of an exit door opening, or the
  center of that point in the corridor where travel to two or  more  exits
  becomes available in two directions.
    (e)  Changes in level. Changes in level requiring less than two risers
  in a corridor shall be by a ramp complying with section 27-377  of  this
  article.  Risers  and  treads  shall  comply  with  the  requirements of
  subdivision (e) of section 27-375 of this article.
    (f) Exterior corridors. Exterior corridors shall be roofed, and  shall
  have  solid  floors  drained to prevent accumulations of standing water.
  Such floors may serve as fire canopies  when  so  constructed.  Exterior
  corridors  shall  be  protected  along  their  outer  side  by guards or
  parapets at least three feet six inches  high.  Openings  in  guards  or
  parapets shall be of such dimensions as to prevent the passage of a five
  inch  dia.  ball.  Where  the outer side of an exterior corridor is more
  than fifty per cent enclosed with solid material, it shall be treated as
  an interior corridor.
    (g) Balconies. Balconies may serve as a means of egress from  dwelling
  units in buildings classified in occupancy group J-2 under the following
  conditions:
    (1) They shall serve at least two dwelling units.
    (2)  They  shall  be  constructed  as required for exterior corridors,
  except that parapets or guards shall not be higher than four feet on the
  outer side of the balcony.

(3) The dwelling units served by balconies shall be separated from each other by construction having at least a two hour fire resistance rating. Such separation shall extend at least three feet beyond the outside face of the exterior wall of the building, although such projection may be reduced to two feet six inches provided that any window opening on each such balcony served by the fire separation shall be at least two inches from such fire separation for every one inch that such separation is less than thirty-six inches. An opening at least twenty inches wide shall be provided between the end of this separation and the balcony parapet or guard, and the opening shall be maintained free and unobstructed for the full height of the balcony, except that privacy screens openable from either side may be permitted in the opening. (4) Access from dwelling units to the balconies shall be through doors having glass panels at least two feet wide and four feet high, without muntins, screens, or other obstructions to hinder entry by breaking the glass panels. The doors shall be lockable only from the inside by devices that can be easily released from the outside after breaking the glass. A combination lock or lock required to be opened by a key or removable device or tool shall not be used. (h) Construction. (1) Interior corridors. Interior corridors shall be completely enclosed within fire separations to provide a minimum fire-resistance rating of one hour except as otherwise provided in subparagraphs a through c of this paragraph: a. For buildings or spaces classified in occupancy group J-1 or J-2 of combustible construction group II exceeding two stories in height, except for buildings not exceeding three stories in height and occupied exclusively by not more than one family on each story without boarders, roomers or lodgers, corridors shall be enclosed within fire separations providing a minimum fire-resistance rating of two hours. b. Corridor partitions may be omitted or may be constructed of unrated noncombustible material in buildings in occupancy group H-2 in the following instances: nurses' stations not exceeding three hundred fifty square feet in area, waiting spaces, lounges and recreational spaces for patients and visitors which do not exceed five hundred square feet in area, spaces used solely for public telephones, and all other spaces which are completely protected by an automatic wet sprinkler system complying with the construction requirements of subchapter seventeen of this code. c. Corridor partitions may be omitted in spaces of occupancy group H-1 used for detention of persons under legal restraint. (2) Exterior corridors and balconies. Exterior corridors and balconies shall be constructed of noncombustible materials. (i) Borrowed lights. No operable transoms shall be permitted in walls of corridors. In corridors required to have a one hour fire-resistance rating, fixed one-quarter inch wire glass panels may be installed in not more than twenty percent of the common wall between the corridor and any room or space, provided that no panel exceeds seven hundred twenty square inches in area; however, openings permitted in paragraph three of subdivision (h) of section 27-370 of this article may be permitted provided all of the limitations and requirements specified in that section are complied with, except that openings in corridor walls serving as fire divisions required to have a fire-resistance rating shall be limited to those specified in section 27-342 of article five of subchapter five of this chapter. (j) Ventilation. Corridors shall be ventilated in accordance with the requirements of subchapter twelve of this chapter. Corridors shall not
be used as open plenums or as ducts to exhaust air from rooms or spaces opening upon them, except as permitted in reference standard RS 13-1. (k) Interior finish. The interior finish of corridors shall be in accordance with the requirements of table 5-4.

Disclaimer: These codes may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.