35-A §755. Clearance reduced

Title 35-A: PUBLIC UTILITIES HEADING: PL 1987, C. 141, PT. A, §6 (NEW)

Part 1: PUBLIC UTILITIES COMMISSION HEADING: PL 1989, C. 502, PT. A, §123 (RP)

Chapter 7-A: OVERHEAD HIGH-VOLTAGE LINE SAFETY ACT HEADING: PL 1995, C. 348, §1 (NEW)

§755. Clearance reduced

If the overhead high-voltage line is covered with a mechanical barrier, in accordance with section 758, the required clearance under section 754, subsections 1 and 2 may be reduced to the designed working dimensions of the mechanical barrier. If the line is de-energized and grounded, in accordance with section 758, subsection 5, the required clearance under section 754, subsections 1 and 2 is reduced from 10 feet to 2 feet. Under no circumstances may the overhead high-voltage line or its covering be contacted. If the overhead high-voltage lines are temporarily raised or moved to accommodate the expected work or other activity, without also being insulated or de-energized and grounded, the required clearance under section 754, subsections 1 and 2 may not be reduced. [1995, c. 348, §1 (NEW).]

SECTION HISTORY

1995, c. 348, §1 (NEW).

Disclaimer: These codes may not be the most recent version. Maine may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.